Produktbeschreibung
TeSys LRD thermal overload relay, 18A/690V, thermal setting range 12-18A, tripping class 10A, for protection of 3-phase motors 7.5kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D18-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).Technische Daten
EAN/GTIN/Barcode | 13389110346838 ; 3389110346831 ; 43389110346839 ; 73389110346830 |
ETIM Klasse Code | EC000106 |
Montageart | Direktanbau |
Einstellbarer Strombereich von: | 12 A |
Einstellbarer Strombereich bis: | 18 A |
Max. Bemessungsbetriebsspannung Ue | 690 V |
Anschlussart Hauptstromkreis | Schraubanschluss |
Anzahl der Hilfskontakte als Öffner | 1 |
Anzahl der Hilfskontakte als Schließer | 1 |
Anzahl der Hilfskontakte als Wechsler | 0 |
Auslöseklasse | CLASS 10 A |
Reset-Funktion Eingang | Nein |
Reset-Funktion automatisch | Ja |
Reset-Funktion Taster | Ja |
Selectra Katalog | INSTA |
Selectra - Markencode | TELM |
Kategoriecode | 5121 |
Ähnliche Produkte
Von dieser Marke