Produktbeschreibung
TeSys LRD thermal overload relay, 32A/690V, thermal setting range 23-32A, tripping class 10A, for protection of 3-phase motors 15kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by EverLink BTR screw terminals , it connects directly to the bottom terminals of 3-pole contactors LC1D40A-D80A. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD96560 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach).Technische Daten
EAN/GTIN/Barcode | 13389119215487 ; 3389119215480 ; 43389119215488 ; 73389119215489 |
Montageart | Direktanbau/Einzelaufstellung |
Einstellbarer Strombereich von: | 23 A |
Einstellbarer Strombereich bis: | 32 A |
Max. Bemessungsbetriebsspannung Ue | 690 V |
Anschlussart Hauptstromkreis | Schraubanschluss |
Anzahl der Hilfskontakte als Öffner | 1 |
Anzahl der Hilfskontakte als Schließer | 1 |
Anzahl der Hilfskontakte als Wechsler | 0 |
Auslöseklasse | CLASS 10 A |
Reset-Funktion Eingang | Nein |
Reset-Funktion automatisch | Ja |
Reset-Funktion Taster | Ja |
Selectra - Markencode | TELM |
Kategoriecode | 5121 |