Micrologic 5.0E (Energy meter) is an electronic control unit used on Masterpact NT 06 to 16 drawout circuit breakers. This control unit has a selective protection (LSI) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0E indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 5.0E is equipped with a digital LCD screen that displays the active energy with 2% accuracy. This control unit can be associated with drawout Masterpact NT basic frame.Technische Daten
EAN/GTIN/Barcode | 3606480344770 |
ETIM Klasse Code | EC000617 |
Polzahl | 4 |
Überlastauslöser Stromeinstellung von: | 252 A |
Überlastauslöser Stromeinstellung bis: | 6300 A |
Anfangswert des unverzögerten Kurzschlussauslöser-Einstellbereiches | 378 A |
Endwert des unverzögerten Kurzschlussauslöser-Einstellbereiches | 63000 A |
Kurzschlussauslöserfunktion | verzögert |
Selectra - Markencode | MERN |
Kategoriecode | 1418 |