Produktbeschreibung
Canalis tap-off unit for KT and KS. It's applied to medium power distribution and TT, IT and TN-S earthing system. The operational voltage is from 230VAC 50/60Hz to 690VAC 50/60Hz. The rated operational current is 100A at 35 ℃. Mounting by Plug-in with fixed polarity with white RAL 9001 surface treatment and whose busbar trunking polarity is 3L + N + PE. It provided protection for size NF fuses (Fuse to be ordered separately). It provided tap-off unit disconnection by right opening the door. Canalis KS busbar trunking compatibility with plug-in outlets, Canalis KT busbar trunking compatibility with KS type plug-in outlets. It provides IP55 protection which conforming to IEC 60529 standard. IK08 conforms to IEC 62262. It is compliant with both IEC 61439-1 and IEC 61439-6. It is also compliant with Green Premium (RoHS/REACH).Technische Daten
EAN/GTIN/Barcode | 13606480005852 ; 3606480005855 ; 73606480005854 |
Breite | 128 mm |
Höhe | 220 mm |
Schutzart (IP) | IP55 |
Farbe | weiß |
Länge | 444 mm |
RAL-Nummer | 9001 |
Polzahl | 5 |
Absicherung | ohne |
Ausführung der Steckdosen | sonstige |
Anzahl der Leiter (ohne Erde) | 4 |
Bemessungsstrom bei AC 50 Hz | 100 A |
Bemessungsspannung bei AC 50 Hz von: | 230 V |
Bemessungsspannung bei AC 50 Hz bis: | 690 V |
Anzahl der sonstigen Steckdosen | 0 |
Anzahl der CEE-Steckdosen | 0 |
Mit Arretierung | Nein |
Phasenselektion | Nein |
Abgangsart | Leitungseinführung |
Anzahl der NEMA-Steckdosen | 0 |
Selectra - Markencode | MERN |
Kategoriecode | 0550 |
Ähnliche Produkte
Von dieser Marke