Produktbeschreibung
REG emergency power supply. To buffer the bus voltage. If a complete mains failure occurs, an external lead gel battery with a voltage of DC 12 V (SELV) can be connected to the REG power supply for buffering. The lead gel battery is recharged or maintained in its charged state by integrated charging electronics. A binary input can be connected in order to register the operational statuses (mains voltage, error warning, battery operation). For installation on DIN rails TH35 according to EN 60715. A data rail is not necessary. Nominal voltage: AC 110-230 V ±10%. Operating voltage: min. AC 92 V - max. AC 253 V. Mains frequency: 50-60 Hz ±10%. Output to power supply: Output voltage: DC 30 V ±2 V. Output current: without battery with mains supply max. 300 mA, with battery without mains supply max. 640 mA. Buffer time with lead gel battery 7,2 Ah: MTN683890: approx. 0.5 h. MTN683832: approx. 1 h. Buffer time with lead gel battery 18 Ah: MTN683890: approx. 1.25 h. MTN683832: approx. 2.5 h. Short-circuit current: Technische Daten
EAN/GTIN/Barcode | 3606485100265 |
Montageart | REG |
Breite in Teilungseinheiten | 4 |
Max. Ausgangsstrom | 640 mA |
Sekundärspannung | 230 mV |
Mit LED-Anzeige | Ja |
Bussystem KNX | Ja |
Bussystem KNX-Funk | Nein |
Bussystem Funkbus | Nein |
Bussystem LON | Nein |
Bussystem Powernet | Nein |
Andere Bussysteme | ohne |
Busspannung pufferbar | Nein |
Anzahl der integrierten Drosseln | 0 |
Anzahl der versorgbaren Linien | 0 |
Selectra - Markencode | MERT |
Kategoriecode | 2511 |