Produktbeschreibung
Canalis tap off unit for KN. It is compatibility with Canalis KN busbar trunking with plug-in outlets. The rated operational voltage is from 230VAC to 500VAC 50/60Hz depending on protective device. The rated operational current is 63A. It provides miniature circuit breaker (MCB) protection and 8 modules of 18mm. Mounting by plug-in with fixed polarity. The tap-off unit polarity is 3L+N+PE, disconnection by opening the door. Door/cover could be open right side. It is suitable for TT, IT and TN-S earthing system. It provides white RAL 9001 surface treatment. Blanking plate could be provided, but circuit breaker to be ordered separately. It provides IP55 protection conforming to IEC 60529. IK08 conforms to IEC 62262. It is compliant with IEC 61439-1 and IEC 61439-6. It is also compliant with Green Premium (RoHS/REACH).Technische Daten
EAN/GTIN/Barcode | 13606480006316 ; 3606480006319 ; 73606480006318 |
Breite | 106 mm |
Höhe | 165 mm |
Schutzart (IP) | IP55 |
Farbe | weiß |
Länge | 344 mm |
RAL-Nummer | 9001 |
Polzahl | 5 |
Absicherung | ohne |
Ausführung der Steckdosen | sonstige |
Anzahl der Leiter (ohne Erde) | 4 |
Bemessungsstrom bei AC 50 Hz | 63 A |
Bemessungsspannung bei AC 50 Hz von: | 230 V |
Bemessungsspannung bei AC 50 Hz bis: | 500 V |
Anzahl der sonstigen Steckdosen | 0 |
Anzahl der CEE-Steckdosen | 0 |
Mit Arretierung | Nein |
Phasenselektion | Nein |
Abgangsart | Leitungseinführung |
Anzahl der NEMA-Steckdosen | 0 |
Selectra - Markencode | MERN |
Kategoriecode | 0550 |